Playbook for distribution DER hosting-capacity limits: voltage rise, reverse flow, and thermal limits from PV and storage. Use to estimate how much DER a feeder can host.

发布者 Codar安全审核通过v0.1.0更新于 2026-11-18

SKILL.md

DER hosting capacity mitigation

Start by identifying the binding constraint, not by assuming it: hosting capacity is set by whichever of voltage, thermal, or protection binds first on this feeder.

Preferred action order

  1. Confirm the binding constraint with feeder snapshots at minimum load / maximum generation (OpenDSS, pandapower): voltage rise along the feeder, reverse flow at the substation, element loading, and regulator behavior.
  2. Use inverter capability first: Volt-VAR and Volt-Watt curves, fixed power-factor settings, or export limits — these are cheap, fast, and usually recover significant headroom.
  3. Adjust feeder controls next: regulator and LTC setpoints (including reverse-power mode behavior), capacitor switching coordination with the new flow patterns.
  4. Re-check protection: reduced relay reach from DER infeed, sympathetic tripping, fuse-recloser coordination, and anti-islanding behavior under high DER output.
  5. Reinforce last: reconductoring, an added regulator, phase rebalancing, or load/DER transfers — and quantify the hosting-capacity gain per upgrade so the cheapest sufficient fix wins.

Working rules

  • Study the minimum-load, maximum-generation snapshot; peak-load studies systematically miss DER constraints.
  • Voltage rise and protection usually bind before thermal on weak feeders — do not stop at a loading check.
  • Validate any fix across the daily profile (or a time-series run), not a single snapshot; Volt-VAR that fixes noon can misbehave at dusk.
  • Legacy regulators may misoperate under reverse flow; check their mode explicitly before relying on them.
  • Route persistent voltage problems to voltage-violation-mitigation and persistent loading problems to thermal-overload-mitigation once the DER-specific levers are exhausted.

Deliver

  • The binding constraint (voltage, thermal, protection) with the numbers and the snapshot that exposed it.
  • The mitigation sequence applied, from inverter settings to reinforcement.
  • The resulting hosting capacity and the first upgrade that buys the next increment.

示例提示词

这条馈线接入光伏后电压越限了,帮我评估还能再接多少DER。

所属插件

电子电气与信息工程面向电气与电子工程研究:电力系统仿真(PSS/E、PSLF、PowerWorld、pandapower、PyPSA、OpenDSS、ANDES)与越限/稳定/短路处置,FPGA 时序收敛与跨时钟域检查,电路与 PCB 设计评审,硬件产品开发流程。

安装该插件会一并获得同领域的 63 个 Skill / MCP。

同插件的其他科研 Skill

常见问题

配电网DER接纳能力治理能做什么?

Playbook for distribution DER hosting-capacity limits: voltage rise, reverse flow, and thermal limits from PV and storage. Use to estimate how much DER a feeder can host。

如何安装配电网DER接纳能力治理?

在科搭 Codar 左侧点击「插件」,在「组件」页签搜索「配电网DER接纳能力治理」并安装;在 Claude Code 或 Codex 中可以发送本页的安装提示词,或下载 Skill 包后解压到 ~/.claude/skills 或 ~/.codex/skills。

配电网DER接纳能力治理需要哪些权限?

该科研 Skill没有声明额外权限;执行具体操作时仍由 Agent 按自身规则请求确认。

配电网DER接纳能力治理经过官方审核吗?

是。SpeedSkills 收录的每个版本都会记录内容摘要与权限声明,当前版本已通过安全审核。